IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3. CAUTION This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.
4. CAUTION – Installation and servicing should be performed by qualified personnel only. De-energize before
opening.
5. DO NOT USE OUTDOORS. The ILB is for use with grounded, UL Listed, damp location rated, indoor fixtures.
Not for use in heated air outlets or hazardous locations.
6. The ILB requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C.
lead.
7. The ILB and A.C. driver must be on the same branch circuit.
8. Do not mount near gas or electric heaters.
9. The ILB should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
10. The ILB will supply 24VDC or 12VDC output at the individual rated specification for 90 minutes. See individual
units for output specifications.
11. Suitable for use in damp locations.
12. For use in 0° C minimum, 50° C maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
ILB
‘A’ MOUNTING DESIGN
EMERGENCY
LIGHTING EQUIPMENT
FOR LED
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 FAX (520) 741-2837
www.iotaengineering.com
Page view 0
1 2 3 4

Summary of Contents

Page 1 - INSTRUCTION MANUAL

IMPORTANT SAFEGUARDSWhen using electrical equipment, basic safety precautions should always be followed, including the following:READ AND FOLLOW ALL S

Page 2 - INSTALLATION INSTRUCTIONS

Page 2INSTALLATION INSTRUCTIONSCAUTION: Before installing, make certain the A.C. power is off and the ILB unit connector is disconnected.1. LED LIG

Page 3 - TESTING & MAINTENANCE

Page 35. LABELS Attach the appropriate labels adjacent to the TBTS. Annotate Replacement Label with identical manufacturer part number(s). The Cautio

Page 4 - TYPICAL WIRING DIAGRAM

Page 4TYPICAL WIRING DIAGRAMFor other diagrams, consult our Customer Service.68612-000 REV 071513ILB WITH TWO PIECE TEST ACCESSORYILBBATTERYPACKRED/W

Related models: ILB-2407 | ILB-1212 | ILB-1207 |

Comments to this Manuals

No comments