IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power
is supplied to the unit.
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnect-
ing the unit connector.
3. CAUTION The integral, high temperature Ni-Cad battery is replaceable. To replace the battery, disconnect the
unit connector and remove both switched and unswitched A.C. power to the fixture. Remove the lid screw and
open the lid to expose the battery. Unplug the battery connector and replace with part number 44203-412 (14.4V
Ni-Cad battery only). Recycle or dispose of the used nickel-cadmium battery properly.
4. DO NOT USE OUTDOORS. The I-160-AC-L is for use with grounded, UL Listed, indoor fixtures except in heated
air outlets or hazardous locations. The acceptability of the combination must be determined by Underwriters
Laboratories. Refer to the Engineering Considerations section for proper installation.
5. The I-160-AC-L requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
6. Do not mount near gas or electric heaters.
7. The I-160-AC-L should be mounted in locations and at heights where it will not readily be subjected to tampering
by unauthorized personnel.
8. The I-160-AC-L is for use with unusually shaped fluorescent fixtures such as wall packs, sconces, and recessed
stair fixtures.
9. The I-160-AC-L will cold strike and operate two 42W 4 pin compact lamps for 90 minutes.
10. The I-160-AC-L operates lamps as follows:
Two 42W 4-pin lamps for 90 minutes at reduced light output.
11. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition
, void
warranty, and result in non-compliance with UL specifications
.
12. Do not use this equipment for other than intended use.
13. Install in accordance with the National Electrical Code and local regulations.
14. Installation and servicing should be performed by qualified personnel.
15. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
I-160-AC-L
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 FAX (520) 741-2837
www.iotaengineering.com
Page view 0
1 2 3 4

Summary of Contents

Page 1 - I-160-AC-L

IMPORTANT SAFEGUARDSWhen using electrical equipment, basic safety precautions should always be followed, including the following:READ AND FOLLOW ALL S

Page 2 - ENGINEERING CONSIDERATIONS

Page 2INSTALLATION INSTRUCTIONSCAUTION: Before installing, make certain the A.C. power is off and the I-160-AC-L unit connector is disconnected.1.

Page 3 - TESTING & MAINTENANCE

Page 36. WIRING THE A.C. INPUT The I-160-AC-L requires an unswitched A.C. power source of either 120 or 277 volts. Select the proper voltage lead an

Page 4 - TYPICAL WIRING DIAGRAMS

Page 4TYPICAL WIRING DIAGRAMSFor wiring diagrams of ballasts not shown, consult our Customer Service.Rev. 03130668160-004WIRING FOR ONE COMPACT LAMP

Comments to this Manuals